Using high-resolution infrared imaging to detect combustible and toxic gases, it features a wide field of view (30° standard) and a maximum detection range of 2km for continuous monitoring of critical areas. Detection sensitivities are verified for quantities of hydrocarbon gas of approximately 2kg at 250m. The system features a long wave infrared (LWIR) camera with a spectral range of 8-14µm (IR) at a spatial resolution of 384x272 pixels. The camera has a standard maximum range of 3,281 feet (1,000 m) and an optional range of up to 6,562 feet (2,000 m). It can detect methane at 0.1 LEL-m, propylene at 0.1 LEL-m, butane at 0.3 LEL-m and propane at 0.5 LEL-m. It operates at a temperature range of 14° to 131°F (-10° to 55°C) and humidity range of 0-95% RH, non-condensing.
General Monitors
949.581.4464
www.generalmonitors.com